If a 120Vac source is used, an appropriately sized resistor must be used in series to limit current to a maximum of 15 Amperes when circuit rating is unknown, or permanent damage may occur.
Step 1: With valve in the CLOSED position, disengage the BOTTOM cam from the splined Hub and rotate Clockwise until SW1 activates. Release cam to re-engage splined Hub.
Step 2: Rotate valve to the OPEN position. Disengage the TOP cam from the splined Hub and rotate Counter-clockwise until SW2 activates. Release cam to re-engage the splined Hub.
Step 3: Cycle valve CLOSED and OPEN several times to insure switches will maintain calibration.
For Reverse Acting actuators:
Step 1: With valve in the CLOSED position, disengage the TOP cam from the splined Hub and rotate Counter-clockwise until SW2 activates. Release cam to re-engage the splined Hub.
Step 2: Rotate valve to the OPEN position. Disengage the BOTTOM cam from the splined Hub and rotate Clockwise until SW1 activates. Release cam to re-engage the splined Hub.
Repeat Step 3 above.
*When using the (4) and (6) switch options, use the same calibration steps as above for the switches you determine to indicate OPEN and which indicate CLOSED.
**Switches may also be set at midpoint, or any point, of travel for Dribble Control, or any other logic necessary for the application.
PRODUCT SPECIFICATIONS
OPTION M
Switch Type Mechanical Sealed Circuitry Termination
Rating
Conforming to standards Contact Resistance Insulation Resistance Switch Type Sealed Circuitry Termination Rating
Conforming to standards Switch Type Sealed Circuitry Termination Rating
Conforming to standards Contact Terminals
No SPDT Quick Connect
10A@125VAC or 250VAC UL: 1054
15M max. (initial) 100M min. (at 500V DC) OPTION K
Mechanical No SPDT Quick Connect 0.1A@125VAC MAX UL: 1054 OPTION TMechanical
No DPDT Quick Connect
8A 125V AC or 250V AC UL recognized and CSA certified, meets MIL-S-8805 Gold or silver End or side
Mechanical Switch Assembly
Switch Option M2/K2/T2
Switch Option M4/K4/T4
Switch Option M6/K6/T6