which is happened in the operating process of a power plant. The cause of fault is analyzed in respect to the design flaw, incorrect closing procedure, inner leakage defect, experience feekback, etc. A series of effective preventive measures are proposed, in order to provide reference for similar events of the same type of units.

generator; third harmonic stator grounding protection; preventive measuresKey words:

中图分类号:TM862 文献标识码:A 文章编号:1008-6226 (2019) 06-0022-03

1 机组概况

某发电公司3期2×330 MW 7,8号燃煤发电机组于2007年投产发电,发电机组型号为QFSN-300-2,冷却方式为水氢氢冷却,其中定子线圈为水内冷,转子线圈、定子铁芯为氢冷。定子线圈冷却水采用除盐水,设计水质要求:电导率,0.5—1.5 μS/cm;pH值(25 ℃),7—8。同时,对发电机内冷水导电度有严格的要求,导电度过大会引起泄漏电流,加速发电机定子线圈绝缘引水管的老化,严重时会使发电机定子发生接地,导致机组跳闸。

势,利用这个特征量可构成100 %定子接地保护,其保护由2部分组成:

(1) 基波零序电压元件,保护范围从机端到中性点85 %范围以上;

(2) 利用三次谐波电势构成定子接地保护,可消除基波零序电压元件保护不到的死区,一般可保护发电机中性点至机端20 %以上的接地故障。

由于发电机中性点附近发生的接地故障电流小,对机组伤害小,不必立即跳闸停机,因此三次谐波定子接地保护一般只投信号,不投跳闸。

在发电机正常运行中,发电机中性点侧的三次谐波电压ΜN3总是大于发电机机端的三次谐波电压ΜS3,假设发电机定子绕组发生单相接地,接地发生在距中性点a范围处,ΜS3及ΜN3随a的变化曲线如图1所示。

2 发电机三次谐波定子接地保护原理

由于发电机的制造原因,无法消除三次谐波电22